Components of IVK MicroTEK-01, MicroTEK-02, MicroTEK-03, MicroTEK-04, MicroTEK-05, MicroTEK-06
| | | |
|
Unit S7-01
It is aimed for metering frequency and quantity of impulses, counting the number of impulses in the time interval when collating pipe piston prover and master flow meter.
It includes: - 2 frequency inputs - 2 impulse inputs - 2 digital inputs with ia spark proof circuit [Exia]IIC - 2 relay outputs
|
|
|
Unit S7-03
It is aimed for metering frequency and quantity of impulses, counting the number of impulses in the time interval when collating pipe piston prover and master flow meter.
It includes: - 2 universal (frequency / impulse) inputs - 3 digital inputs for general purposes
|
|
|
Unit S9-01
It is aimed for metering unified current signal (4-20) mA and temperature with thermal resistance TSM-50,TSM-100, TSP-50, TSP-100, TSP-500, Pt100 ( NSH GOST Р 8.625-2006 ), thermal couples THK, THA (NSH GOST Р 8.525-2001).
It includes: - 1 thermal input with ia spark proof circuit [Exia]IIC - 2 inputs (4-20)mА with ia spark proof circuit [Exia]IIC
|
|
|
Unit S9-02
It is aimed for metering standardized current signal (4-20) mA.
It includes: - 3 inputs (4-20)mA with ia spark proof circuit [Exia]IIC
|
|
|
Unit S9-03
It is aimed for metering standardized current signal (4-20) mA.
It includes: - 4 inputs (4-20)mA with ia spark proof circuit [Exia]IIC
|
|
|
Unit S9-04
It is aimed for metering signals from temperature sensors TSM-50,TSM-100, TSP-50, TSP-100, TSP-500 (NSH GOST Р 8.625-2006), thermal couple THK, THA (NSH GOST Р 8.585-2001).
It includes: - 4 thermal inputs with ia spark proof circuit [Exia]IIC
|
|
|
|
|
|
|