Accessories for Electric Equipment

VKV.a Explosion Proof Cable Terminal

It is aimed for equipping the explosion proof electric equipment with d protection; it is provided with 1ExdIIC Х protection. Letter X in the end of the explosion protection marking means that the following is to be provided:

A) VKV.a cable terminals cab be used for armored cable with laced metal armor, with wire armor and belt armor (but for lead armor) B) For IIC equipment it is possible to use VKV.a cable terminals if the size of the explosion proof enclosure is not exceeding 2000 cu.cm.

VKV.a cable terminal is aimed to be used under UHL conditions, category 1, as per GOST 15150-69 by the ambient temperature from -60 up to +80 ºС.

Technical Parameters and Description

 Range of application in explosion hazard zones as per GOST R 51330.9 

1.2

 Explosion protection type

1ЕхdIIС Х

 Operation temperature ranges, ºС

from -60 to +80

 Environmental protection as per GOST 14254

IP 67

 Material

brass
galvanized steel

 Thread

metric (m) GOST 8724
conical pipe (k) GOST 6211
cylindrical pipe (t) GOST 6357

Technical Parameters

Type

Dimensions,mm

Diameter of inner cable sheath, D, not armored,mm
min-max

Diameter of outer cable sheath, D, mm
min-max

Casing tightening torque pos. 3, at most, Nm

Weight, g

Casing material

L

А

M

VKV.а.s.m-1

80

34

М20х1.5

6 - 12

8 - 17

9±1

230

steel

VKV.а.s.m-2

80

41

М25х1.5

9 - 17

14 - 25

9±1

295

steel

VKV.а.s.m-3

90

48

М32х1.5

17 - 23

23 - 32

13±1

425

steel

VKV.а.s.m-4

90

63

М40х1.5

23 - 29

29 - 39

14±1

785

steel

VKV.а.l.m-1

80

34

М20х1.5

6 - 12

8 - 17

9±1

270

brass

VKV.а.l.m-2

80

41

М25х1.5

9 - 17

14 - 25

9±1

340

brass

VKV.а.l.m-3

90

48

М32х1.5

17 - 23

23 - 32

13±1

450

brass

VKV.а.l.m-4

90

63

М40х1.5

23 - 29

29 - 39

14±1

810

brass

VKV.а.s.t-1

80

34

G ½ -A

6 - 12

8 - 17

9±1

230

steel

VKV.а.s.t-2

80

41

G ¾- A

9 - 17

14 - 25

9±1

295

steel

VKV.а.s.t-3

90

48

G 1- A

17 - 23

23 - 32

13±1

425

steel

VKV.а.s.t-4

90

63

G 1 ¼ -A

23 - 29

29 - 39

14±1

785

steel

VKV.а.l.t-1

80

34

G ½ -A

6 - 12

8 - 17

9±1

270

brass

VKV.а.l.t-2

80

41

G ¾- A

9 - 17

14 - 25

9±1

340

brass

VKV.а.l.t-3

90

48

G 1- A

17 - 23

23 - 32

13±1

450

brass

VKV.а.l.t-4

90

63

G 1 ¼ -A

23 - 29

29 - 39

14±1

810

brass

VKV.а.s.k-1

80

34

R ½

6 - 12

8 - 17

9±1

230

steel

VKV.а.s.k-2

80

41

R ¾

9 - 17

14 - 25

9±1

295

steel

VKV.а.s.k-3

90

48

R 1

17 - 23

23 - 32

13±1

425

steel

VKV.а.s.k-4

90

63

R 1 ¼

23 - 29

29 - 39

14±1

785

steel

VKV.а.l.k-1

80

34

R ½

6 - 12

8 - 17

9±1

270

brass

VKV.а.l.k-2

80

41

R ¾

9 - 17

14 - 25

9±1

340

brass

VKV.а.l.k-3

90

48

R 1

17 - 23

23 - 32

13±1

450

brass

VKV.а.l.k-4

90

63

R 1 ¼

23 - 29

29 - 39

14±1

810

brass

VKV.а.l.m-4С

94

67

M40x1.5

26 - 33.5

29 - 39

14±1

830

brass

Exterior View and Overall Dimensions

  1. Shank
  2. Seal
  3. Casing
  4. Cone ring
  5. Clamping ring
  6. Seal
  7. Washer
  8. Clamp

Designation Example in Placing Order

Explosion Proof Cable Terminal VKV.а.l.t-3 TU 3449-622-20885897-2006