Explosion-proof multiturn RemTEK-03 electric drives with electronic torque and position limitation are aimed to regulate pipeline valves and fittings with diameter from 100 to 1200 mm, in explosion hazardous areas of class 1 and 2 as per GOST P 51330.9-99 in severe operating conditions with the extended ambient temperature ranges (from minus 60 to plus 50 °С).
Application - Shut-off and control valves, stop valves (wedge valves, sliding shutter etc), including emergency shutdown system (ESD).
There are three basic modifications of Rem-TEK-03 electric drive being manufactured as per ways of control and power supply:
- on the basis of BUR control module (S type) with in-built noncontact reversing-type starter and smooth start function
- on the basis of BUR control module (M type) with external reversing-type starter and smooth start function
- on the basis of BUR control module (R type) with external reversing-type starter and smooth start function
|
Basic Functions
- Pipeline valves control with switching off as per position and torque
- Smooth start (S and M types of control modules)
- Dynamic braking mode with accurate stops in any position (S type of control module)
- Complete protection of the electric motor
- Digital signaling and control
- Control by in-built desk or remote control panel
- Internal interfaces RS-485 (Modbus RTU and Profibus DP) and CAN
- Analog valve position signal (4...20mA)
Technical Parameters
Explosion protection marking
|
1ExdIIBT4
|
Protection class
|
IP67
|
Ambient temperature, °C
|
from -60 to +50
|
R, M modifications control module supply voltage, V
|
220 (-50%, +47%)
|
S modification control module and all electric drives modifications power circuits supply voltage , V
|
380 (-50%, +47%)
|
|
|
Features
- RemTEK-03 electric drive includes BUR control module with SCR's control for electric motor smooth start and dynamic braking with setting up torque limitation in three zones: start, moving and stopping
- Torque measuring and limiting with the help of in-built algorithms as per measured electric motor parameters
- Setting up ESD and fire systems trip points
- Auxiliary output terminal for electric drive external testing or emergency change-over to the desired position (ESD system, fire system)
|
Main Modifications of RemTEK-03 Electric Drives
Modification
|
Type of mounting seat
|
Rotation torque ranges, N·m
|
Output element rate at the torque 50 % out of max., rpm
|
Capacity of electric motor, kW
|
Rated amperage, А
|
Maximum amperage, А
|
RemTEK-03.B.3000.30.5.X
|
B
|
30…300
|
30
|
0.55
|
1.8
|
10.8
|
RemTEK-03.B.3000.60.5.X
|
B
|
30…300
|
60
|
1.1
|
2.7
|
17.6
|
RemTEK-03.B.600.40.5.X
|
B
|
60...600
|
40
|
1.5
|
5.2
|
33.8
|
RemTEK-03.B.600.40.5.X
|
C
|
60...600
|
40
|
1.5
|
5.2
|
33.8
|
RemTEK-03.C.800.96.5.X
|
C
|
80...800
|
96
|
5.5
|
12.5
|
90
|
RemTEK-03.C.1000.20.5.X
|
C
|
100...1000
|
20
|
1.5
|
4.7
|
22.6
|
RemTEK-03.C.1000.48.5.X
|
C
|
100...1000
|
48
|
4
|
8.5
|
59.5
|
RemTEK-03.D.4000.15.5.X
|
D
|
400...4000
|
15
|
4
|
11
|
78.8
|
RemTEK-03.D.5000.7.5.5.X
|
D
|
500...5000
|
7.5
|
2.5
|
5.6
|
29.5
|
RemTEK-03.D.5000.15.5.X
|
D
|
500...5000
|
15
|
5.5
|
12.5
|
90
|
RemTEK-03.E.7000.12.5.X
|
E
|
700...7000
|
12
|
5.5
|
12.5
|
90
|
RemTEK-03.E.10000.6.5.X
|
E
|
1000...10000
|
6
|
4
|
8.5
|
59.5
|
RemTEK-03.E.10000.12.5.X
|
E
|
1000...10000
|
12
|
7.5
|
14.8
|
111
|
X - control module modification (R, M, S) depending on the way of motor control
|
Components
- Electric drive control module BUR
- Electric motor AIM-A and DATEK-250
- Hand wheeled gearbox
- Valves adapters (if necessary)
|
Auxiliary Equipment
- Communication unit MKS-07М
- Communication unit PI-04Т
- Remote Control Panel
|
|
Check List
Certificates and Permits
|