russian english german
 

RemTEK-03 Electric Drive

Explosion-proof multiturn RemTEK-03 electric drives with electronic torque and position limitation are aimed to regulate pipeline valves and fittings with diameter from 100 to 1200 mm, in explosion hazardous areas of class 1 and 2 as per GOST P 51330.9-99 in severe operating conditions with the extended ambient temperature ranges (from minus 60 to plus 50 °С).    

Application - Shut-off and control valves, stop valves (wedge valves, sliding shutter etc), including emergency shutdown system (ESD).

There are three basic modifications of Rem-TEK-03 electric drive being manufactured as per ways of control and power supply:

  • on the basis of BUR control module (S type) with in-built noncontact reversing-type starter and smooth start function
  • on the basis of BUR control module (M type) with external reversing-type starter and smooth start function
  • on the basis of BUR control module (R type) with external reversing-type starter and smooth start function

Basic Functions

  • Pipeline valves control with switching off as per position and torque
  • Smooth start (S and M types of control modules)
  • Dynamic braking mode with accurate stops in any position (S type of control module)
  • Complete protection of the electric motor
  • Digital signaling and control
  • Control by in-built desk or remote control panel
  • Internal interfaces RS-485 (Modbus RTU and Profibus DP) and CAN
  • Analog valve position signal (4...20mA)

 

Technical Parameters

 Explosion protection marking

1ExdIIBT4

 Protection class

IP67

 Ambient temperature, °C

from -60 to +50

 R, M modifications control module supply voltage, V

220
(-50%, +47%)

 S modification control module and all electric drives modifications power circuits supply voltage , V

380
(-50%, +47%)

 

Features 

  • RemTEK-03 electric drive includes BUR control module with SCR's control for electric motor smooth start and dynamic braking with setting up torque limitation in three zones: start, moving and stopping
  • Torque measuring and limiting with the help of in-built algorithms as per measured electric motor parameters
  • Setting up ESD and fire systems trip points
  • Auxiliary output terminal for electric drive external testing or emergency change-over to the desired position (ESD system, fire system)

Main Modifications of RemTEK-03 Electric Drives

Modification

Type
of mounting
seat

Rotation
torque
ranges, N·m

Output
element
rate at the torque
50 % out of max., rpm

Capacity
of electric motor,
kW

Rated
amperage, А

Maximum
amperage, А

 RemTEK-03.B.3000.30.5.X

B

30…300

30

0.55

1.8

10.8

 RemTEK-03.B.3000.60.5.X

B

30…300

60

1.1

2.7

17.6

 RemTEK-03.B.600.40.5.X

B

60...600

40

1.5

5.2

33.8

 RemTEK-03.B.600.40.5.X

C

60...600

40

1.5

5.2

33.8

 RemTEK-03.C.800.96.5.X

C

80...800

96

5.5

12.5

90

 RemTEK-03.C.1000.20.5.X

C

100...1000

20

1.5

4.7

22.6

 RemTEK-03.C.1000.48.5.X

C

100...1000

48

4

8.5

59.5

 RemTEK-03.D.4000.15.5.X

D

400...4000

15

4

11

78.8

 RemTEK-03.D.5000.7.5.5.X

D

500...5000

7.5

2.5

5.6

29.5

 RemTEK-03.D.5000.15.5.X

D

500...5000

15

5.5

12.5

90

 RemTEK-03.E.7000.12.5.X

E

700...7000

12

5.5

12.5

90

 RemTEK-03.E.10000.6.5.X

E

1000...10000

6

4

8.5

59.5

 RemTEK-03.E.10000.12.5.X

E

1000...10000

12

7.5

14.8

111

X - control module modification (R, M, S) depending on the way of motor control

Components

- Electric drive control module BUR

- Electric motor AIM-A and DATEK-250

- Hand wheeled gearbox

- Valves adapters (if necessary)

Auxiliary Equipment

- Communication unit MKS-07М

- Communication unit PI-04Т

Remote Control Panel

 

Check List

Certificates and Permits

Our website uses cookies to ensure you get the best experience on our website. By continuing to browse this site you agree to our use of cookies.