|
|
Power Supply Unit IP-15-01, IP-15-02
Power Supply Unit IP-15-01
|
Is aimed for power supply to units with spark proof circuits of explosion protection marking [Ex ia] IIC as per GOST Р51330.0, GOST 51330.10. IP-15-01 has output voltage channels for 24V and 12V. IP-15-01 is to be installed outside hazardous indoor premices on dust and moist proof cabinets.
|
Features
- Extended ranges of incoming circuit voltage
- Protection from impulse circuit interference
- Two galvanically isolated outputs
- Enhanced strength of isolation between output and input
- Output voltage adjustment
- Protection of output current overrun
- Extended temperature ranges
- Indication of operation state
- Compact casing
|
|
Main Technical Parameters
Input Parameters:
|
Ranges of input voltage, V
|
~ 110...275
|
Ferquency of feeding circuit, Hz
|
50 ±3
|
Maximum current, consumed from circuit (at 220 V), A
|
0.45
|
Withstand overvoltage by the input, V
|
~ 288 (20 sec.) ~ 323 (1 sec.)
|
Withstand microsecond overvoltage by the input, kV (GOST Р 51317.4.5-99, IEC 61000-4-5, EN 61000-4-5)
|
4 (L,N-PE) 2 (L-N)
|
Output parameters:
|
Output channel, 24 V
|
Output voltage, V
|
24 ±3
|
Ranges of output monophase voltage, V
|
22...26
|
Permissible ripple voltage, V, not exceeding
|
0.15
|
Maximum output current, A
|
1.5
|
Output channel, 12 V
|
Output voltage, V
|
12 ±3
|
Permissible ripple voltage, V, not exceeding
|
0.1
|
Maximum output current, A
|
0.5
|
Insulation parameters:
|
Insulation voltage between incomining and outcoming circuits, V
|
2500
|
Insulation voltage between incomining circuits and casing, V
|
1500
|
Insulation voltage between outcomining circuits and casing, V
|
500
|
Isolation voltage between output channels, V
|
500
|
Parameters:
|
Ambient temperature, ºC
|
-40...+50
|
Cooling
|
natural convection
|
Average touble free life, hours, not less
|
50 000
|
Type of fastening
|
DIN 35 bar
|
Dimensions, mm
|
102×115×47
|
Weight, kg, not exceeding
|
0.4
|
|
|
|
Power Supply Unit IP-15-02
|
It is aimed for power supply to units with spark proof circuits of explosion protection marking [Exia] IIC as per GOST Р51330.0, GOST 51330.10. IP-15-01 is to be installed outside explosive hazardous premises into dust and humid proof cabinets.
|
Features
- Enhanced strength of isolation between output and input
- Protection from impulse circuit interference
- Protection of output current overrun
- Enhanced output capacity
- Indication of operation state
|
|
Technical Parameters
Input Parameters:
|
Ranges of input voltage, V
|
~ 187...245
|
Frequency of feeding circuit, Hz
|
50 ±3
|
Maximum current, consumed from circuit (at 220 V), A
|
0.5
|
Withstand overvoltage by the input, V
|
~ 288 (20 sec.) ~ 323 (1 sec.)
|
Withstand microsecond overvoltage by the input, kV (GOST Р 51317.4.5-99, IEC 61000-4-5, EN 61000-4-5)
|
4 (L,N-PE) 2 (L-N)
|
Output parameters:
|
Output voltage, V
|
18...34
|
Permissible ripple voltage, V, not exceeding
|
5
|
Maximum load current, A
|
2
|
Insulation parameters:
|
Insulation voltage between incoming and outcoming circuits, V
|
2500
|
Insulation voltage between incoming circuits and casing, V
|
1500
|
Insulation voltage between outcoming circuits and casing, V
|
500
|
General Parameters:
|
Operational temperature ranges, °С
|
+1...+50
|
Cooling
|
natural convection
|
Average trouble free life, hours, not less
|
50 000
|
Type of fastening
|
screw fastening
|
Dimensions, mm
|
180×165×110
|
Weight, kg, not exceeding
|
3.5
|
|
|
|
|
|
|
|