russian english german
 

Examples of SSU Application

Power Control Cabinet for power equipment of Oil Metering System
SSU-100А-00/06-04/04/02/00-0-0-0-UKhL4

The equipment to be connected

Electric consumers of SIKN process unit:

  • Valve electric drive
  • Fan electric drive
  • Electrical explosion-proof heaters
  • Lightning (outdoor , working and emergency one)

Electric consumers of SIKN electrics unit:

  • Auxiliary Equipment Cabinet
  • Control Cabinet
  • Operator's workstation
  • Electrical heaters
  • Lightning (working and emergency one)
  • Socket network
  • Repair network

Functions

  • Power distribution, connected lines protection from overloading and short circuit
  • Provision of automatic, manual local and manual remote mode for equipment control
  • Indication of connected lines status on cabinet front panel
  • Group lines separation over facilities wherein they are located
  • Automatic shutdown of selected equipment groups belonging to process and electric equipment units on fire alarm or gaseousness signal incoming from PCS
  • Variable-frequency control of pumps rotation speed. Control is carried out by means of Hitachi J200 frequency converter (PCh). PCh control is performed by BR-03 control blocks produced by SME TEC Ltd. There is also RS485 Modbus RTU outlet to connect with PCS

Construction

SSU is a cabinet dimensioned as 600x1800x(+200-socket)x600 mm (WxHxD). Cable inlet from below. Components of the firms mentioned below were used as electrics components: WAGO, Finder, Phoenix Contact, IEK etc. Components are located on main and side mounting panels of cabinet. Elements for indication and power consumer control are located on cabinet's door. Inlet and outlet of connected lines are performed through screw terminals.

Cabinet Exterior View and Arrangement

Technical Parameters

Parameter

Value

 Input AC voltage, V

380

 Input Nominal Current, А

100

 Number of power consumers to be connected:

 

    - 220V AC consumers, pcs.

6

    - 380V AC consumers, pcs.

10

 Nominal current of lines to be connected, А

6 - 25

 Earthing type

TN - S

 Inlet line maximum section, mm2

35

 Maximum section, mm2, of electric consumers' lines to be connected 

10

 Cabinet protection class

IP54

 Climatic version

UKhL4

 Dimensions (width x height x depth), mm

600х2000х600

 
 

Power Control Cabinet for Equipment of Gas and Water Metering Units
SSU-60А-07/06-02/00/00/00-0-0-0-UKhL4

The Equipment to be Connected

Electric consumers of gas metering unit:

  • Fan electric drive
  • Electrical heaters
  • Lightning (outdoor , working and emergency one)
  • Electric drive of smoke removal valve

Electric consumers of water metering unit:

  • Fan electric drive
  • Lightning (working and emergency one)

Functions

  • Power distribution, protection of lines to be connected from overloading and short circuit
  • Provision of automatic, manual local and manual remote mode for equipment control
  • Status indication of lines to be connected on cabinet front panel
  • Group lines separation over facilities wherein they are located
  • Automatic shutdown of selected equipment groups belonging to process and electric equipment units on fire alarm or gaseousness signal incoming from PCS

Construction

SSU is a cabinet for cantilever erection dimensioned as 600x1800x(+200-socket)x600 mm (WxHxD). Cable inlet from below. Components of the firms mentioned below were used as electrics components: WAGO, Finder, Phoenix Contact, IEK etc. Elements of indication and power consumer control are located on cabinet's door. Inlet and outlet of lines to be connected are performed through screw terminals.

Cabinet Exterior View and Arrangement

Technical Parameters

Parameter

Value

 Input AC voltage, V

380

 Input nominal current, А

60

 Number of power consumers to be connected:

 

  - 220V AC consumers, pcs.

23

   - 380V AC consumers, pcs.

2

 Nominal current of lines to be connected, А

1 - 25

 Earthing type

TN - S

 Inlet line maximum section, mm2

35

 Maximum section, mm2, of electric consumers' lines to be connected 

10

 Cabinet protection class

IP54

 Climatic version

UKhL4

 Dimensions (width x height x depth), mm

600х1000х250